GOVERNMENT POLYTECHNIC BHUJ · Electrical Engineering Department

CO5 Audited Virtual Lab: IBR-Integrated Feeder Protection

Directional supervision and adaptive overcurrent setting groups for a current-limited solar-PV source

Switchgear and ProtectionDI05009011 Semester 5Academic Year 2026–27 Balanced 3-Phase RMS ModelOffline Browser Lab
CO5: Implement modern techniques to mitigate fault challenges in networks integrated with renewable energy sources.

Experiment

To analyse protection challenges created by a current-limited solar-PV inverter in a radial distribution feeder and apply directional supervision and adaptive relay setting groups.

Aim

Calculate balanced three-phase fault currents, determine the currents measured by primary and backup relays, evaluate IEC IDMT operating times, and verify selective circuit-breaker operation.

Learning outcomes

  • Compare conventional-grid and inverter fault-current behaviour.
  • Identify reverse-current sympathetic-tripping risk.
  • Check pickup security, fault sensitivity and grading margin.
  • Apply explicit setting groups and directional supervision.

Case A

Downstream feeder fault with PV disconnected.

Case B

Upstream bus fault with remote PV and fixed non-directional protection.

Case C

Repeat Case B with directional and adaptive protection.

Deliberate scope: This audited version uses a balanced three-phase RMS fault. Unbalanced faults are not represented by arbitrary multipliers; they require positive-, negative- and zero-sequence networks plus an inverter sequence-control model.

Theory

Grid fault current

The grid is represented by a positive-sequence Thevenin impedance obtained from short-circuit level and X/R ratio. For a downstream fault, the impedance of the feeder section up to the fault is included.

|Zs| = VLL² / Ssc

Igrid = Vphase / |Zs + Zline + Rf|

Inverter fault response

The PV inverter is represented as either a current-limited ride-through source or momentary cessation. The ride-through current is based on rated current and the selected current limit, not multiplied directly by solar operating power.

Ipv,rated = Ppv / (√3 VLL)

Ipv,fault = klim × Ipv,rated

IEC IDMT relay

t = TMS × k / [(I / Ipickup)^α − 1]

Curvekα
IEC Standard Inverse0.140.02
IEC Very Inverse13.51.0
IEC Extremely Inverse802.0
Adaptive setting groups: SG-A is used without PV; SG-B is explicitly entered and selected when PV is connected. No hidden setting multiplier is applied.
Directional supervision: R2 is blocked when current flows in reverse from a remote PV source toward an upstream bus fault.

Pre-Test

1. Compared with a synchronous source, a grid-connected inverter fault current is generally:

2. For selective feeder protection, the relay nearest the downstream fault should:

3. A directional element is needed to distinguish:

4. An adaptive relay setting group changes according to:

5. Relay pickup should normally be:

Single-Line Diagram and Ratings

Network ratings appear here.
GRID50 MVA SCThevenin source R1 BackupCB1 SOURCE BUS R2 PrimaryCB2 LOAD2 MWRadial feeder 5 km feeder SOLAR PVDisconnected Orange: forward grid current · Purple: reverse PV current
Grid fault current
balanced RMS
PV contribution
ride-through/cessation
R1 measured current
backup relay
R2 measured current
primary relay
R1 operating time
IEC IDMT
R2 operating time
IEC IDMT
Grading margin
relevant relay pair
First breaker
predicted operation
Select a preset or parameters, then run the simulation.

Effective settings and calculated impedances

Values appear after simulation.
Relay currents and breaker operation
IEC relay operating-time comparison

Procedure

1
Select A: No PV feeder fault. Verify that R2 operates before R1 and that the grading margin is adequate.
2
Select PV at source bus. Compare the PV contribution, R2 current and operating time with Case A.
3
Select B: Reverse-feed risk. A remote PV source feeds an upstream bus fault through R2 in reverse direction.
4
Observe whether the fixed non-directional R2 trips sympathetically before R1.
5
Select C: Directional mitigation. Verify that R2 is blocked for reverse current and R1 clears the bus fault.
6
Select PV momentary cessation. Compare its zero PV fault contribution with current-limited ride-through.
7
Change SG-A and SG-B settings. Ensure pickup security, fault sensitivity and grading margin are all acceptable.
8
Add observations, export CSV, complete the post-test and generate the conclusion.

Observation Table

CasePV statusPV response/locationFault zoneIgrid (A)Ipv (A)IR1 (A)IR2 (A)tR1 (s)tR2 (s)Margin (s)GroupMethodResult

Post-Test

1. The audited model does not use fixed multipliers for L-G and L-L faults because:

2. During momentary cessation, the PV fault-current contribution in this model is:

3. For a remote-PV upstream bus fault, directional supervision should:

4. SG-B is selected in adaptive mode when:

5. A secure pickup check requires pickup to exceed:

Methodology Audit

Removed from the first version
  • Unjustified fixed factors for L-G, L-L and L-L-G fault currents.
  • PV fault current multiplied directly by solar operating percentage.
  • Source impedance treated as purely resistive.
  • Hidden adaptive-setting multipliers.
  • Arbitrary 30-second cap on IEC relay time.
  • Feeder impedance incorrectly included in an upstream bus fault.
Implemented in this audited version
  • Balanced positive-sequence three-phase RMS fault model.
  • Grid short-circuit level with explicit X/R decomposition.
  • Current-limited ride-through or momentary cessation.
  • Explicit SG-A and SG-B relay settings.
  • IEC SI, VI and EI curves without hidden time clipping.
  • Pickup security, sensitivity and grading checks.
Use limitation: This is an educational phasor-domain laboratory. It is not an EMT inverter model, relay commissioning tool, CT-saturation model, arc-flash study, or utility-grade protection-setting package.

Result and Conclusion

No conclusion generated yet.

Suggested result statement

A current-limited inverter-based resource can change the magnitude, location and direction of fault-current contribution. Fixed non-directional overcurrent protection may operate undesirably when a remote PV source feeds an upstream fault. Explicit adaptive setting groups improve coordination for changing operating conditions, while directional supervision prevents reverse-current sympathetic tripping.

References used to frame the educational model

  • MathWorks, “Overcurrent Relay Protection in AC Microgrid” — relay coordination, phase/earth protection and standard IEC/IEEE characteristics.
  • National Renewable Energy Laboratory, “Protection” — inverter fault responses differ from synchronous generators and can provide only a small amount above rated current or cease current rapidly.
  • NREL/NLR studies on IBR controls and relay elements — current limiting, momentary cessation and operating conditions affect protection response.