METHODOLOGY AUDIT — TRANSFORMER DIFFERENTIAL VIRTUAL LAB ======================================================== OVERALL VERDICT --------------- The revised V2 model is methodologically suitable for diploma-level concept demonstration and comparative virtual-lab exercises. It is not suitable for actual transformer-protection setting, relay commissioning, or publication-grade transient validation. CRITICAL ISSUES FOUND IN THE FIRST VERSION ------------------------------------------ 1. The transformer kVA and voltage ratings were only displayed; they did not affect the calculations. 2. Relay currents were generated directly from arbitrary multiples of 5 A, without transformer rated-current or CT-ratio conversion. 3. Internal phase and earth faults used unexplained fixed coefficients. 4. A trip time was calculated using an invented expression that was not tied to a manufacturer relay characteristic. 5. CT saturation was represented without clearly stating that it was only a simplified magnitude-loss approximation. 6. The transformer rating text overlapped the relay area and was not clearly visible. CORRECTIONS IMPLEMENTED ----------------------- 1. Three-phase rated winding currents are calculated from I = S/(sqrt(3)V). 2. HV and LV CT primary ratios are entered explicitly with a fixed 5 A secondary rating. 3. CT secondary currents are calculated from actual winding currents and CT ratios. 4. Numerical compensation refers both sides to a common 5 A base and corrects the selected tap mismatch. 5. Internal faults use a user-defined HV contribution percentage; the two in-zone contributions add in the differential element. 6. The dual-slope biased operating threshold is continuous at the breakpoint. 7. Manufacturer-specific trip-time prediction was removed. The lab reports operating margin instead. 8. Inrush blocking uses the entered second-harmonic percentage and threshold only for the inrush scenario. 9. Assumptions and methodological boundaries are displayed inside the laboratory. ACCEPTABLE SIMPLIFICATIONS -------------------------- - Single RMS-current magnitude per side rather than phase-by-phase phasors. - Vector-group phase compensation is assumed already completed by the numerical relay. - External fault is represented by selected through-current in per unit. - CT saturation is represented by reduced fundamental-current magnitude, not a transient waveform. - Internal earth fault does not include an explicit zero-sequence network or restricted-earth-fault element. WHAT THE LAB MAY VALIDLY DEMONSTRATE ------------------------------------ - Current balance in healthy operation. - Stability of percentage-biased differential protection during external through current. - Possible false differential current caused by CT error, mismatch, or severe saturation. - Differential operation for an in-zone internal fault. - Security improvement from numerical ratio/tap compensation. - Inrush security from second-harmonic restraint. WHAT MUST NOT BE CLAIMED ------------------------ - Exact fault-current magnitude for a real transformer installation. - Exact relay operating time. - Exact CT transient saturation behaviour. - Complete phase-shift, zero-sequence, or vector-group performance. - Suitability of the displayed settings for a real transformer.